The TA-A8041-D and TA-8042-D CO2 sensors are designed to be mounted through the side of a duct or plenum. The sensor is typically mounted in the return air duct or plenum near or at the air handler prior to the introduction of outdoor air. The sensor outputs a 0-10 VDC signal for CO2 and is compatible with any GreenTrol controller that accepts an analog output CO2 sensor.
CO2 MEASUREMENT
Non-Dispersive Infra Red (NDIR) CO2 Measurement with ABC Logic
Use with GreenTrol outdoor airflow controllers to provide advanced CO2-DCV or ASHRAE 62.1 compliant population-based DCV
Demonstrate compliance with ASHRAE Standards 62.1, 90.1 and 189.1
Satisfy LEED requirements
Maintain acceptable indoor air quality
Save energy
Features
NDIR CO2 sensing technology
0 to 2,000 ppm range
ABC logic ensures long-term calibration stability
0-10 VDC output
Insertion probe design
4 inch (8041) and 8 inch (8042) probe lengths available
Install in ducts or in plenums
Compatible with all GreenTrol application specific controllers that accept an analog input from a CO2 sensor
Connects directly to the power input terminals of compatible GreenTrol application controllers
Overview
The TA-A8041-D and TA-8042-D CO2 sensors are designed to be mounted through the side of a duct or plenum.
The sensor is typically mounted in the return air duct or plenum near or at the air handler prior to the introduction of outdoor air.
When combined with a GreenTrol outdoor air controller, this CO2 sensor can be used to improve traditional CO2 demand
control ventilation by using a unique control algorithm that resets the outdoor air setpoint between user defined upper and lower airflow limits (not damper positions) to maintain the space CO2 level. This control method eliminates the under- and overventilation that is prevalent with traditional CO2-DCV.
An even more advanced control method uses the measured airflow rate and CO2 level to estimate the population and calculates the required outdoor airflow, thus meeting the actual requirements of ASHRAE Standard 62.1.
ABC logic ensures years of calibration free operation in applications where the population goes to near zero during
unoccupied periods.
Functionality
CO2 Measurement: Provides the CO2 level to the analog input of a GreenTrol application controller that accepts an analog CO2 sensor input
CO2 Sensor
Technology: Telaire Non Dispersive Infrared (NDIR)
Range: 0 to 2,000 ppm
Required Duct Air Velocity: 0 to 1,500 FPM [7.62 m/s]
Accuracy: ±30 ppm plus 3% of reading, @72° F [22°C]
Temperature Dependence: 0.36% FS/°F [0.2% FS/°C]
Pressure Dependence: 0.33% of reading per 0.1 in. [2.54 mm] Hg
Stability: <2% of FS over life of sensor (10 year typical)
Response Time: <3 minutes for 90% step change typical
Warmup Time: 2 minutes operational, 10 minutes to achieve maximum accuracy
Analog Output
AO1
Assignment: Linear CO2 output signal
Range: 0-10VDC
Environmental Limits, Power Requirements & Dimensions
Environmental Limits
Temperature: 32 to 122 ⁰F [0 to 50 ⁰C]
Humidity: 5 to 95%
Power Requirement: 24 VAC (22.8 to 26.4 under load) @1.65V-A
Flammability Classification: UL-94V-5
Dimensions
Probe Length
TA-A8041-D: 4.09 in. [103.8 mm]
TA-A8042-D: 8.07 in. [205.1 mm]
Junction Box: 3.05H x 3.05W x 1.58D in. [74.6 x 74.6 x 4.02 mm]